Understanding heat pump COP and seasonal efficiency

A COP of 3 means the heat pump delivered three units of heat for one unit of electricity under the conditions stated. Before you use that figure to estimate a bill, find out whether it came from a single test, a standard season or measurements from a whole heating system.

· Published · Reviewed

Read the small print beside the number

A manufacturer’s COP belongs to a particular set of source and output temperatures. Compare two machines at the same test temperatures. SCOP is a seasonal coefficient based on a defined set of conditions. A seasonal performance factor, or SPF, can be an installer’s design estimate or a ratio measured over time. Ask which it is.

If one figure covers the compressor alone and another includes the electricity for domestic hot water or backup, the two figures answer different questions. Ask for a description of the meters or calculation alongside the headline number.

Why two weeks averaging 3 and 4 don’t necessarily give 3.5

Imagine one week when the system delivers 300 kWh of heat for 100 kWh of electricity. Another week it delivers 40 kWh for 10 kWh. Those weekly ratios are 3 and 4. Across both weeks, the measured performance is 340 ÷ 110, or about 3.09. The week when much more electricity went through the system has more influence.

Take totals from the heat and electricity meters for the same dates and with the same equipment included. Dividing the combined totals gives you a performance ratio for that period. Two weeks, however carefully measured, still don’t describe a whole year.

A question to take back to the installer

“Does this include hot water, backup and pumps, and is it measured or forecast?” With that answer you can compare it with an equivalent figure. To translate a seasonal estimate into annual electricity, use the guide to heat pump kWh.

Sources and further reading

Browse heat pumps

How to report an error or outdated information