How this calculation works
Calculate the useful heat added to the water. Divide by each heat source’s efficiency or seasonal performance and apply the appropriate unit rate.
How to use your result
Use performance specific to hot water where available. A heat pump may run at a different temperature and efficiency for hot water than for rooms.
Does not calculate system standing losses, separate sterilisation cycles, fixed charges or equipment costs unless included in the input assumptions.
Worked example
For 5.23 kWh of water heat, a heat pump at 2.5 needs about 2.09 kWh of electricity.
Starting assumptions
- Water to heat per use · 120 litres
- Incoming cold water temperature · 12 °C
- Target water temperature · 55 °C
- Times per week · 7 uses
- Seasonal boiler efficiency · 88 %
- Electric system efficiency · 100 %
- Seasonal performance factor · 3 ratio
The examples give you a starting point. Use your own measurements and tariffs for a decision.
Sources
- NIST liquid water heat capacity
- Energy Technology List seasonal heat pump performance
- UK Standard Assessment Procedure
Methodology reviewed · Revision 1